HoodEx
← Blog

Baffle Filter vs Mesh Filter: Which Belongs in a Commercial Kitchen Hood?

9 November 2026 · 4 min read

The filters are the first thing cooking grease meets on its way out of the kitchen. They look like a small part of the hood, but the type you have and the state it is in decide how much grease travels on into the duct and the fan. Most commercial hoods use baffle filters, and many home hoods use mesh. Here is why, and what it means for cleaning.

How each filter works

A baffle filter is a row of overlapping metal channels. Air has to change direction several times to get through, and the heavier grease droplets cannot make the turns, so they hit the metal and run down into a trough or grease cup. A mesh filter is layers of woven aluminium. Grease is caught in the holes of the mesh and stays there until someone washes it out.

Baffle filterMesh filter
Usual placeCommercial canopy hoodsHome range hoods and some light-duty units
How grease is heldRuns off into a trough or cupTrapped inside the mesh
Airflow when dirtyFalls graduallyFalls quickly as the holes close up
MaterialStainless steel, galvanised steel or aluminiumUsually aluminium
CleaningHot soak in degreaser, then rinseRegular washing, gentle on aluminium

Why commercial kitchens use baffle filters

A mesh filter holds its grease in one packed layer right next to the hot air stream, which is a poor place for fuel to sit. NFPA 96, the standard most commercial kitchens follow, calls for listed grease filters and does not accept mesh filters as the grease-removal device in a commercial hood. If a commercial hood in your kitchen has mesh panels fitted, ask your hood supplier whether they are right for that hood. Your insurer or local authority may have its own requirements too.

Signs a filter needs attention

  • Grease dripping from the filter face instead of draining to the trough
  • Smoke hanging under the hood when the fan is running
  • Filters that feel sticky soon after washing
  • Gaps between filters, or a missing filter, so air bypasses them altogether
  • Bent channels, cracked frames or a warped filter that no longer sits flush

Fit matters as much as type

A clean filter only works if all the air goes through it. Filters should sit tight in their track, side by side, with no empty slots. Fit them with the channels running vertically so grease can drain. A gap of a few centimetres lets grease-laden air straight into the duct, and that grease ends up where you cannot see it.

When to clean and when to replace

Filters in a busy kitchen usually need washing daily to weekly; our guide on cleaning baffle and grease filters covers the soak method. Replace a filter when it is bent out of shape, corroded through or no longer seals in its track. Strong caustic chemicals can pit aluminium filters, so check the material before you soak them.

HoodEx cleans exhaust filters on their own or as part of the complete exhaust system service. Contact HoodEx and we will arrange an inspection.

Frequently asked questions

Can I put mesh filters in a restaurant hood?

Commercial hoods are normally fitted with listed baffle-type grease filters, and NFPA 96 does not accept mesh filters as the grease-removal device. Check with your hood supplier before changing the filter type.

Which way should baffle filters face?

With the channels running vertically, so grease can drain down into the trough or cup.

Do clean filters mean the duct is clean?

No. Filters catch much of the grease, but some always gets past them and settles in the duct and fan, which need cleaning separately.

Need your exhaust system cleaned?

HoodEx cleans the full system — hood, filters, duct, fan and ESP unit — across the UAE. See our services or the areas we serve.

Book a Cleaning
+971 56 391 1944WhatsAppGet Quote